VIMATHERM industrial exchanger is a dismantlable gasketed plate heat exchangers with flange connections. A pack of plates, usually made of Stainless Steel, is placed between two very thick carbon steel end plates. The whole is guided by a roller assembly and pressed by several tie rods to obtain its watertightness.
VIMATHERM heat exchanger consists of:
Depending on the working data, the four connections can be either all four on the fixed head or two on the fixed head and two on the movable pressure plate.
VT28 | VT45 | VT60 | VT100 | VT110 | VT130 | VT170 | |
---|---|---|---|---|---|---|---|
Connexion | DN100 | DN100 | DN150 | DN150 | DN300 | DN250 | DN400 |
Maximum flow(m³/h) | 150 | 150 | 400 | 400 | 1500 | 1000 | 2500 |
Distance between plates (en mm) | 4 | 4 | 4 | 4 | 3,5 | 3,5 | 4 |
Maximum number of plates | 300 | 300 | 400 | 400 | 500 | 500 | 500 |
Surf./plates (m²) | 84 | 135 | 240 | 240 | 550 | 650 | 850 |
Maximum pressure (bar) | 25 | 25 | 25 | 25 | 25 | 25 | 25 |
Lht | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Hht | H1 | H2 | L2 | L3 | L4 | Frame 51 | Frame 101 | Frame 151 | Frame 201 | Frame 251 | |
VT28 |
1235 |
1071 |
189 |
500 |
234 |
133 |
835 |
1085 |
1335 |
1585 |
1835 |
VT45
|
1655 |
1491 |
189 |
500 |
234 |
133 |
835 |
1085 |
1335 |
1585 |
1835 |
VT60 |
1780 |
1555 |
275 |
660 |
310 |
175 |
1095 |
1395 |
1695 |
1995 |
2295 |
VT100 |
2500 |
2275 |
275 |
660 |
310 |
175 |
1105 |
1405 |
1705 |
2005 |
2305 |
VT110 |
2050 |
1676 |
356 |
1125 |
600 |
262,5 |
1420 |
1720 |
2020 |
2320 |
2620 |
VT130 |
2320 | 1970 |
320 |
940 |
480 |
230 |
1420 |
1720 |
2020 |
2320 |
2620 |
VT170 | 2750 | 1965 | 315 | 1380 | 700 | 340 | 1420 | 1720 | 2020 | 2320 | 2620 |