GASKETS


All VIMATHERM plates, in their original version, include gaskets which have leakage indicators to prevent any mixing of primary and secondary fluids without prior detection.
In case a gasket is accidentally torn, if this occurs on the external part, there is automatically an outward leak. If this occurs on the internal part, the leakage grooves are designed so as the leakage can be detected on the outside.



PLATES

With a regular recovery system on a heat exchanger, if a plate is pierced through, a mixing occurs between the primary fluid and the secondary fluid. Two systems can be offered for a better safety and to reveal defective plates:

- A booster pump can be added at the end of the rising recovery to maintain a higher pressure on the way back on the descending recovery.

- System with an intermediary loop with a lower pressure to avoid that water from the loop goes into the process product.